Sensor Types
NAMUR Sensors, Dry Contacts
Detection level for ON
>2.1 mA
Detection Level for Off
<1.2 mA
Channel Impedance
1kOhm ±10%
Wetting Voltage
8V DC ±1V DC
Fault Detection capable
NAMUR Sensors or field resistor pack, Guaranteed short circuit: <100 Ω , Guaranteed good status: 360 Ω to 20 kΩ , Guaranteed open circuit: > 75 kΩ
Isolation
Galvanically isolated according to EN 60079-11. Voltage peak value 375V DC.
CHARM power req.
28 mA max @ 24V DC ±10%
CHARM Heat Dissipation
0.57 W
Configurable channel type
Dry contact or discrete state sensor changing <2 Hz