Detection Level for On
> 10 V DC
Detection Level for Off
< 5 V DC
Wetting Current
6 mA @ 24 V DC
Input Impedance
4 kΩ (approximately)
Isolation
Galvanically isolated and factory tested to 1000 V DC
CHARM Power Req.
12 mA max @ 24 V DC
CHARM Heat Dissipation
0.32 W
CHARM Heat Dissipation
0.32 W
Configurable Channel Type
Discrete Input - Dry contact or discrete state sensor changing <2 Hz, Pulse Count - Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width
Field Circuit Protection
Recommend External Fuse at power source, Field wiring disconnect